?? direct.dat
字號:
3Twi: inlet water temperature
2Wa: dry air mass flow rate
3Tai: inlet dry bulb air temperature
8Hai: inlet air humidity ratio
3Two: outlet water temperature (same as OUT(1))
3Tao: outlet air temperature (same as OUT(2))
8Hao: outlet air humidity ratio (same as OUT(3))
3Two: outlet water temperature
3Tao: outlet air dry bulb temperature
8Hao: outlet air humidity ratio
7Qt: total cooling load
7Qs: sensible cooling load
4fw: wet fraction of coil surface area
#
1Ic: coil type: 0=flat continuous fins, 1=circular fins
2Ap: primary (tube exterior) surface area (m2)
3As: secondary (fin) surface area (m2)
4Ai: internal surface area (m2)
5Am/Af: ratio of minimum air flow area to face area (-)
6kf: fin material thermal conductivity [kW/(m K)]
7Af: coil face area (m2)
8Nf: number of fins per centimeter
9Np: number of tubes per row
10Nr: number of rows
11Do: outside tube diameter (m)
12Di: inside tube diameter (m)
13Delta: fin thickness (m)
14Cm: thermal cap. (mass * sp. heat) of coil (kJ/K)
15Sl: tube row spacing in air flow direction (m)
16Df: fin diameter if par(1)=1 or length if par(1)=0 (m)
17Dc: coil depth in air flow direction (m)
18kt: tube thermal conductivity [kW/(m K)]
19FR: water flow row: FR=0.5 or 1 or 2 or 3. (-)
*
13THREE-WAY MERGE VALVE WITH PNEUMATIC ACTUATOR
7 1 6 3 9
2W1: inlet mass flow rate, port 1 (open if C = 1)
2W2: inlet mass flow rate, port 2 (open if C = 0)
3T1: inlet temperature, port 1
3T2: inlet temperature, port 2
4C: control variable from controller
4Ca: actuator relative position
4Ca: actuator relative position
3T3: outlet temperature
4Cs: valve stem relative position
#
1K1: port 1 flow resistance when fully opened, open if C=1 [1000/(kg m)]
2K2: port 2 flow resistance when fully opened, open if C=0 [1000/(kg m)]
3Rammda: leakage parameter (-)
4Tau: actuator time constant (sec)
5hys: hysteresis parameter (-)
6Mode: for ports 1,2: 0=lin/lin, 1=exp/lin, else=exp/exp
7flow network index which this unit belongs to
8order index of flow branch 1 in the network
9order index of flow branch 2 in the network
*
14EVAPORATIVE HUMIDIFIER
0 0 3 3 1
3Tai: inlet air temperature
8Hai: inlet air humidity ratio
2Wai: inlet moist air mass flow rate
8Hao: outlet air humidity ratio
3Tao: outlet air temperature
2Wao: outlet moist air mass flow rate
#
1h*A: water to air heat transfer coeff * area (kW/C)
*
15ROOM MODEL
9 4 8 6 6
2W: mass flow rate of ventilation air
3Tai: ventilation air inlet temperature
3Tm: temp of fully mixed air [same as OUT(1)]
3Tw: wall mass temperature [same as OUT(2)]
3Ti: interior mass temperature [same as OUT(3)]
3Tp: spatial avg. air temp., piston flow [OUT(4)]
7Qw: conduction heat flow into wall mass
7Qi: heat flow due to internal gains
3Tm: temperature of fully mixed portion of air
3Tw: wall mass temperature
3Ti: interior mass temperature
3Tp: spatial avg. air temp., piston flow
3Tr: average room air temperature
3Tao: exhaust air temperature
#
1V: volume of room air mass (m3)
2MwCw: thermal capacitance of walls (kJ/C)
3MiCi: thermal capacitance of interior mass (kJ/C)
4Hw: heat transfer coeff * area for wall mass (kW/C)
5Hi: heat transfer coeff * area for interior mass (kW/C)
6f: fraction of air mass which is fully mixed
*
16STICKY PROPORTIONAL CONTROLLER (FOR USE BETWEEN SUPERBLOCKS)
3 0 2 1 3
4Ctm: measured controlled variable
4Cts: controlled variable setpoint
4C: controller output signal
#
1Kp: proportional gain (-)
2B: error band (-)
3Ko: offset (-)
*
17MIXING DAMPERS AND MERGE
2 0 6 1 7
2W1: mass flow rate, inlet 1 (C= 0 => closed)
2W2: mass flow rate, inlet 2 (C= 0 => open)
3T1: temperature at inlet 1 (C= 0 => damper closed)
3T2: temperature at inlet 2 (C= 0 => damper open)
4C: input control signal: relative damper position
3T3: outlet temperature
3T3: outlet temperature
#
1Ko1: flow resistance 1 when damper is open [1000/(kg m)]
2Ko2: flow resistance 2 when damper is open [1000/(kg m)]
3Rammda: leakage parameter (-)
4Wf: weighting factor: 0=exp., 1=lin., or 0 < Wf < 1
5flow network index which this unit belongs to
6order index of flow branch 1 in the network
7order index of flow branch 2 in the network
*
18PLENUM (MULTI-WAY MIXING BOX)
0 0 20 1 1
2W1: inlet mass flow rate 1
2W2: inlet mass flow rate 2
2W3: inlet mass flow rate 3
2W4: inlet mass flow rate 4
2W5: inlet mass flow rate 5
2W6: inlet mass flow rate 6
2W7: inlet mass flow rate 7
2W8: inlet mass flow rate 8
2W9: inlet mass flow rate 9
2W10: inlet mass flow rate 10
3T1: inlet temperature 1
3T2: inlet temperature 2
3T3: inlet temperature 3
3T4: inlet temperature 4
3T5: inlet temperature 5
3T6: inlet temperature 6
3T7: inlet temperature 7
3T8: inlet temperature 8
3T9: inlet temperature 9
3T10: inlet temperature 10
3Tout: outlet temperature
#
1N: number of flow streams merging (-)
*
19PSYCHROMETRICS
0 0 5 6 1
3T: inlet air dry bulb temperature
8Rh: if MODE=1, inlet relative humidity
8H: if MODE=2, inlet humidity ratio
3Tw: if MODE=3, inlet air wet bulb temperature