?? da02040a.gsd
字號:
;******************************************************************************************************************************
;* GSD-File for: Danfoss Drives A/S *
;* FC 300 Series DPV1 *
;* *
;* File name: DA02040A *
;* *
;* Contact: Danfoss Drives A/S *
;* DK 6300 Graasten *
;* Denmark *
;* Hotline: Int. + 45 74 88 61 00 *
;* E-mail: Drives_Hotline@danfoss.com *
;* *
;* Revision: 23-03-2004: Rev. 1.00 FC300 GSD file created. *
;* 06-01-2005: Rev. 2.00 FC300 GSD file changes. *
;* ExtUserPrmData & DPV1 Alarm implemented *
;* 28-06-2005: Rev. 2.01 Removed comment line ;0x1,0x06,.... *
;* 07-11-2005: Rev. 2.02 SSA support added *
;* 17-08-2006: Rev. 2.10 New ExtUserPrmData added *
;* 15-11-2006: Rev. 2.11 New FC102/FC202 added, new alarms added *
;* 27-04-2007: Rev. 2.12 Diagnostic_alarm_supp changed to 0 *
;* *
;******************************************************************************************************************************
#Profibus_DP
GSD_Revision = 3;
Vendor_Name = "DANFOSS DRIVES A/S";
Model_name = "FC100/200/300"
Revision = "Rev. 2.12"
Ident_Number = 0x040A;
Protocol_Ident = 0;
Station_type = 0;
FMS_supp = 0;
Hardware_Release = "5.0"
Software_Release = "4.38"
Bitmap_Device="FC"
Bitmap_Diag="FCSF"
Bitmap_SF="FCSF"
Slave_Family = 1@Danfoss@FC100/200/300
Info_Text = "FC100/200/300 series revision 2.12"
9.6_supp = 1;
19.2_supp = 1;
93.75_supp = 1;
187.5_supp = 1;
500_supp = 1;
1.5M_supp = 1;
3M_supp = 1;
6M_supp = 1;
12M_supp = 1;
MaxTsdr_9.6 = 15;
MaxTsdr_19.2 = 15;
MaxTsdr_93.75 = 15;
MaxTsdr_187.5 = 15;
MaxTsdr_500 = 15;
MaxTsdr_1.5M = 25;
MaxTsdr_3M = 50;
MaxTsdr_6M = 100;
MaxTsdr_12M = 200;
Redundancy = 0;
24V_Pins = 0;
Freeze_Mode_supp = 1;
Sync_Mode_supp = 1;
Auto_Baud_supp = 1;
Set_Slave_add_supp = 1;
Min_Slave_Intervall = 06;
Modular_Station = 1;
Max_Module = 1;
Max_Input_Len = 28;
Max_Output_Len = 28;
Max_Data_Len = 56;
Max_Diag_Data_Len = 38;
Fail_Safe = 1;
DPV1_Slave = 1;
;ALARM
Alarm_Type_Mode_supp = 1;
Diagnostic_Alarm_supp = 0;
Process_Alarm_supp = 0;
Pull_Plug_Alarm_supp = 0;
Status_Alarm_supp = 0;
Update_Alarm_supp = 0;
Manufacturer_Specific_Alarm_supp = 0;
Alarm_Sequence_Mode_Count = 0;
Extra_Alarm_SAP_supp = 0;
Diagnostic_Alarm_required=0;
Process_Alarm_required=0;
Pull_Plug_Alarm_required=0;
Status_Alarm_required=0;
Update_Alarm_required=0;
Manufacturer_Specific_Alarm_required =0;
;DPV1 specific
C1_Read_Write_supp = 1
C2_Read_Write_supp = 1
C1_Max_Data_Len = 240
C2_Max_Data_Len = 240
C1_Response_Timeout = 100
C2_Response_Timeout = 100
C1_Read_Write_required = 0
C2_Read_Write_required = 0
C2_Max_Count_Channels = 3
Max_Initiate_PDU_Length = 52
DPV1_Data_Types = 0
WD_Base_1ms_supp = 1
Check_Cfg_Mode = 0
Publisher_supp = 1
; Autoconfig
PrmText=1
Text(0)="Disable Autoconfig"
Text(1)="Enable Autoconfig"
EndPrmText
PrmText=2
Text(0)="None"
Text(302)="Minimum Reference"
Text(303)="Maximum Reference"
Text(312)="Catch up/slow Down"
Text(341)="Ramp 1 Ramp up Time"
Text(342)="Ramp 1 Ramp Down Time"
Text(351)="Ramp 2 Ramp up Time"
Text(352)="Ramp 2 Ramp down Time"
Text(380)="Jog Ramp Time"
Text(381)="Quick Stop Ramp Time"
Text(411)="Motor Speed Low Limit [RPM]"
Text(413)="Motor Speed High Limit [RPM]"
Text(416)="Torque Limit Motor Mode"
Text(417)="Torque Limit Generator Mode"
Text(590)="Digital & Relay bus control"
Text(593)="Pulse Out term. 27 bus control"
Text(595)="Pulse Out term. 29 bus control"
Text(653)="Terminal 42 Output bus control"
Text(890)="Bus Jog 1 Speed "
Text(891)="Bus Jog 2 Speed"
Text(1680)="Fieldbus CTW"
Text(1682)="Fieldbus REF"
Text(3401)="PCD 1 Write to MCO"
Text(3402)="PCD 2 Write to MCO"
Text(3403)="PCD 3 Write to MCO"
Text(3404)="PCD 4 Write to MCO"
Text(3405)="PCD 5 Write to MCO"
Text(3406)="PCD 6 Write to MCO"
Text(3407)="PCD 7 Write to MCO"
Text(3408)="PCD 8 Write to MCO"
Text(3409)="PCD 9 Write to MCO"
Text(3410)="PCD 10 Write to MCO"
EndPrmText
PrmText=3
Text(0)="None"
Text(1472)="VLT Alarm Word"
Text(1473)="VLT Warning Word"
Text(1474)="VLT Ext. Status Word"
Text(1500)="Operating Hours"
Text(1501)="Running Hours"
Text(1502)="kWh Counter"
Text(1600)="Control Word"
Text(1601)="Reference [Unit]"
Text(1602)="Reference % "
Text(1603)="Status Word"
Text(1605)="Main Actual Value [%]"
Text(1610)="Power [kW]"
Text(1611)="Power [hp] "
Text(1612)="Motor Voltage"
Text(1613)="Frequency"
Text(1614)="Motor Current"
Text(1615)="Frequency [%]"
Text(1616)="Torque [Nm]"
Text(1617)="Speed [RPM]"
Text(1618)="Motor Thermal"
Text(1619)="KTY sensor temperature"
Text(1622)="Torque [%]"
Text(1630)="DC Link Voltage"
Text(1632)="Brake Energy /s"
Text(1633)="Brake Energy /2 min"
Text(1634)="Heatsink Temp."
Text(1635)="Inverter Thermal"
Text(1638)="SL Controller State"
Text(1639)="Control Card Temp."
Text(1650)="External Reference"
Text(1651)="Pulse Reference"
Text(1652)="Feedback [Unit]"
Text(1653)="Digi Pot Reference"
Text(1660)="Digital Input"
Text(1661)="Terminal 53 Switch Setting"
Text(1662)="Analog Input 53"
Text(1663)="Terminal 54 Switch Setting"
Text(1664)="Analog Input 54"
Text(1665)="Analog Output 42 [mA]"
Text(1666)="Digital Output [bin]"
Text(1667)="Freq. Input #29 [Hz]"
Text(1668)="Freq. Input #33 [Hz]"
Text(1669)="Pulse Output #27 [Hz]"
Text(1670)="Pulse Output #29 [Hz]"
Text(1671)="Relay Output [bin]"
Text(1672)="Counter A"
Text(1673)="Counter B"
Text(1674)="Precise Stop Counter"
Text(1675)="Analog In X30/11"
Text(1676)="Analog In X30/12"
Text(1677)="Analog Out X30/8 [mA]"
Text(1684)="Comm. Option STW"
Text(1685)="FC Port CTW 1"
Text(1690)="Alarm Word"
Text(1691)="Alarm Word 2"
Text(1692)="Warning Word"
Text(1693)="Warning Word 2"
Text(1694)="Ext. Status Word"
Text(3421)="PCD 1 Read from MCO"
Text(3422)="PCD 2 Read from MCO"
Text(3423)="PCD 3 Read from MCO"
Text(3424)="PCD 4 Read from MCO"
Text(3425)="PCD 5 Read from MCO"
Text(3426)="PCD 6 Read from MCO"
Text(3427)="PCD 7 Read from MCO"
Text(3428)="PCD 8 Read from MCO"
Text(3429)="PCD 9 Read from MCO"
Text(3430)="PCD 10 Read from MCO"
Text(3440)="Digital inputs MCO"
Text(3441)="Digital outputs MCO"
Text(3450)="Actual position"
Text(3451)="Commanded position"
Text(3452)="Actual master position"
Text(3453)="Slave index position"
Text(3454)="Master index position"
Text(3455)="Curve position"
Text(3456)="Track error"
Text(3457)="Synchronizing error"
Text(3458)="Actual velocity"
Text(3459)="Actual master velocity"
Text(3460)="Synchronizing Status"
Text(3461)="Axis status"
Text(3462)="Program status"
Text(3470)="MCO Alarm word 1"
Text(3471)="MCO Alarm word 2"
EndPrmText
ExtUserPrmData=1 "Auto Configuration"
Bit(0) 0 0-1
Prm_Text_Ref=1
EndExtUserPrmData
ExtUserPrmData=2 "PNU in P915/0"
Unsigned16 1680 1680-1680
Prm_Text_Ref=2
EndExtUserPrmData
ExtUserPrmData=3 "PNU in P915/1"
Unsigned16 1682 1682-1682
Prm_Text_Ref=2
EndExtUserPrmData
ExtUserPrmData=4 "PNU in P915/2"
Unsigned16 0 0-3500
Prm_Text_Ref=2
EndExtUserPrmData
ExtUserPrmData=5 "PNU in P915/3"
Unsigned16 0 0-3500
Prm_Text_Ref=2
EndExtUserPrmData
ExtUserPrmData=6 "PNU in P915/4"
Unsigned16 0 0-3500
Prm_Text_Ref=2
EndExtUserPrmData
ExtUserPrmData=7 "PNU in P915/5"
Unsigned16 0 0-3500
Prm_Text_Ref=2
EndExtUserPrmData
ExtUserPrmData=8 "PNU in P915/6"
Unsigned16 0 0-3500
?? 快捷鍵說明