隨著光伏發電系統快速發展,以及電動汽車充電樁的普及,傳統的剩余電流保護器無法滿足實際需求。介紹了一款B型剩余電流保護器,采用磁調制剩余電流互感器和零序電流互感器采集剩余電流。根據GB/T 22794—2017標準要求,可識別1 kHz及以下的正弦交流、帶和不帶直流分量的脈動直流、平滑直流等剩余電流信號。經信號調理電路將電壓信號送到單片機進行采集和判斷。通過試驗測試,該樣機在測試精度和速度上均符合國家標準的相關要求。The rapid development of photovoltaic power generation systems and the popularity of electric vehicle charging piles make the traditional residual current protective devices unable to meet the actual demand.This paper proposed a type B residual current protective device,which uses the magnetically modulated residual current transformer and the zero sequence current transformer to acquire the residual current.According to the requirements of GB/T 22794—2017,the type B residual current protective device can detect sinusoidal AC residual current of 1kHz and below 1kHz,pulsating DC residual current with and without DC component,smooth DC residual current and so on.The signal processing circuit sends the voltage signal to the MCU for acquisition and judgment.Through experimental tests,the device meets the relevant requirements of national standards in terms of test accuracy and speed.
標簽:
電流保護器
上傳時間:
2022-03-27
上傳用戶:
漏電保護器的工作原理:漏電保護器主要包括檢測元件(零序電流互感器)、中間環節(包括放大器、比較器、脫扣器等)、執行元件(主開關)以及試驗元件等幾個部分。三相四線制供電系統的漏電保護器工作原理示意圖。TA 為零序電流互感器,GF 為主開關,TL為主開關的分勵脫扣器線圈。在被保護電路工作正常,沒有發生漏電或觸電的情況下,由克希荷夫定律可知,通過TA 一次側的電流相量和等于零,即:這樣TA 的二次側不產生感應電動勢,漏電保護器不動作,系統保持正常供電。當被保護電路發生漏電或有人觸電時,由于漏電電流的存在,通過TA一次側各相電流的相量和不再等于零,產生了漏電電流Ik。在鐵心中出現了交變磁通。在交變磁通作用下,TL二次側線圈就有感應電動勢產生,此漏電信號經中間環節進行處理和比較,當達到預定值時,使主開關分勵脫扣器線圈TL 通電,驅動主開關GF 自動跳閘,切斷故障電路,從而實現保護。用于單相回路及三相三線制的漏電保護器的工作原理與此相同,不贅述。
標簽:
漏電保護器
工作原理
接線方式
上傳時間:
2013-10-19
上傳用戶:zhangjinzj